Transcript 0:00 [upbeat music] This is Mike Roberts with Roberts Corrosion Services, and this is the episode to discuss Article Seventy-Five: MIC, A Positive Vial Is Not a Diagnosis. 0:14 The first thing I always notice when I open this article is the picture at the top. 0:19 It's somebody collecting solids and sludge out of a pig receiver into a cut-apart plastic bucket, which is not what I'd call a sterile container [chuckles]. 0:28 I took that picture, and it has always made me cringe a little because that's the step where internal corrosion sampling goes wrong before it even starts. The correct way to sample is sterile sample bottles every time, 0:43 not most of the time. That's how you keep from cross-contaminating a sample. If you're sampling out of different receivers, you don't reuse the same container to draw things out of. 0:55 You don't even reuse the same container at the same site because a lot happens to that sludge the minute it comes out of the pipeline. It hits the air, the temperature changes, the pressure changes. 1:07 There's a whole issue on that in the archive, The Sample Won't Wait, and the line in there is, "Don't let one bottle do the job of four." Internal corrosion sampling is a difficult enough thing to do correctly. 1:20 If you contaminate it right off the bat, it really doesn't matter how good you are at it. Now, this article actually came about because of a conversation I had with a colleague in the industry. 1:32 He asked me when I would determine that something was MIC. What was my threshold? How far would I go down the rabbit hole before I said, "Okay, this has to be MIC"? 1:44 That sparked some memories because we have an on-site lab at our office, so we see things labeled MIC quite often. 1:52 Usually, it's off a bacteria test, and we have a one-page document that lists out what it actually takes to call something MIC. It started as an internal document at RCS. 2:03 It's built pretty closely on the NACE standards for this, TM0106 and TM0212. 2:11 It lists the three conditions we're looking for before we'll label something MIC, where that methodology comes from, what we cite, what evidence people should look for, a few suggestions, and some of the common traps people run into. 2:24 I'd handed it out before. I gave one to my colleague when he asked. When we got done drafting the article, it just seemed appropriate to attach that document, too. 2:34 So this is one of the articles on the newsletter site that has a download with it. We'll come back to that at the end. 2:41 So that's what this episode is about, what a positive vial actually tells you and what it takes to call something MIC. The article starts the way most of ours do, with a real-world situation. 2:54 I like putting somebody in a place that I've been in a hundred times because a lot of times corrosion techs get tossed into situations like that, and that's especially true with internal corrosion. 3:06 Most of the time, internal corrosion falls in the lap of the corrosion technician or the corrosion engineer, and it's not something you deal with every day. 3:15 External corrosion, cathodic protection, interference, that type of stuff you deal with all the time, rectifier inspections, test station inspections, all of that. 3:26 Every once in a while, you get a phone call from a pig run, or they're replacing a section of pipe and there are fluids coming out of the cutout. 3:33 They've pushed some sludge out and they want it tested, and you're generally trying to figure it out on the way to the project. So picture it. 3:42 You pulled the samples off the receiver a month ago, fluids in sterile bottles, solids scraped into their own container, everything inoculated into the kit vials in the truck ready for the lab. 3:53 The phenol red vials you counted two weeks ago, three of them went yellow. Now it's day twenty-eight. The SRB vials are finally readable, and four of those came back black. 4:05 You write the counts on the form and send it up the ladder, and the next time you hear about it, somebody has typed one word into the corrosion cause field, MIC. 4:15 That step, inoculating the vials, is just us screening for bacteria levels in the sludge, and one of the most common things we see, sometimes in our own lab, is some of the SRB vials turn, or most of them, or all of them by the end of the twenty-eight days and somebody just labels that MIC. 4:33 It seems like a catch-all. If there was bacteria involved, it must be MIC, so people throw it right on there, and sometimes it sticks. 4:42 That leads to biocides and inhibitors and other treatments and whole internal corrosion programs having to change. Here's the thing. 4:50 The standard that tells you how to grow those bacteria also tells you in the second paragraph of its own scope that growing them settles nothing on its own. 4:59 TM0194 says, "The presence of bacteria in a system does not necessarily indicate that they are causing a problem, and populations causing problems in one system may be harmless in another. 5:12 Bacterial population determinations are one more diagnostic tool." One more tool, not the verdict. I think a lot of people aren't even aware of that. 5:24 It is perfectly fine to have some bacteria in some cases in some situations. There are bacteria everywhere in the world on everything. The presence of bacteria doesn't mean the bacteria is causing a problem, 5:39 and because internal corrosion sampling falls on people who don't do it every week, the interpretation rules deserve more attention than they usually get. The field procedure is the easy half. 5:52 Both MIC standards open their interpretation sections with nearly the same sentence. That's not an accident. 5:59 TM0212 says that because microorganisms are ubiquitous, their presence does not necessarily indicate a causal relationship with the internal corrosion observed in a pipeline. It goes further. 6:13 Microorganisms may nearly always be cultured from natural environments, so merely detecting viable organisms in samples associated with corrosion does not necessarily prove that MIC has occurred. 6:25 The external surfaces standard says the same thing about the outside of the pipe. So a positive result is close to the expected result. Be just as careful with the opposite reading. 6:38 TM0194 lists several reasons a culture can come back negative that have nothing to do with the condition of the pipe. A vial only grows the organisms that can use its nutrients. 6:51 Oxygen picked up during sampling hampers anaerobes. Only a small percentage of the viable bacteria in a sample can be recovered by any single medium. And some bacteria can't be grown in culture media at all. 7:05 And one more I should have mentioned earlier, the salinity of the vials matters. When clients order bacteria kits from us, they tell us what salinity percent they want, and there's a reason for that. 7:17 If the bacteria are living in high salinity water and you inject them into a low salinity medium or the other way around, you can kill them just by inoculating the vials. 7:27 The media has to be appropriate for the conditions the bacteria are actually growing in. No growth may be a fact about your medium rather than a fact about the system. 7:38 What I see a lot is people see that trigger, the vials turning, and they immediately want to inject something, an inhibitor, a biocide, something to kill the bacteria because that's what's causing the internal corrosion. 7:51 It may not be, and they haven't done their due diligence to make sure it's actually a real problem. 7:58 Eckert's Field Guide to Internal Corrosion Mitigation and Monitoring for Pipelines makes the point with the bluntest line in the literature. Its second MIC rule reads, "Bacteria tests are not MIC tests." 8:12 I wanna take a pause and say that again. Bacteria tests are not MIC tests. If you have a positive bacteria test, it does not mean you have MIC. 8:22 That's hard for people to accept because they relate the two as being one and the same, and they're really not. The first rule in that set is the constructive version. 8:32 MIC has to be understood using both microbiological and corrosion data. TM0212 says the same thing. MIC cannot be evaluated or diagnosed solely with microbiological data. 8:45 And when it comes to actually determining a cause, the standard shifts into mandatory language. 8:51 All chemical, microbiological, metallurgical, and operational data about the pipeline must be examined, integrated, and analyzed. So what would actually be MIC? 9:04 If we're involved in a project and we're looking into this, it starts with a little bit of homework and a little bit of history. 9:11 And then when the sampling and testing happens, we're also looking at some other sampling and testing. The article goes into three conditions, and these are very important. 9:22 If you don't meet these conditions, it is very difficult to say it's actually MIC. And here's a problem a lot of operators run into. 9:32 If you yourself have already called it MIC, then when you're in an audit and the auditor is looking at what you're doing for your internal corrosion program, they're just going to accept that it's MIC. 9:43 They're not going to prove you wrong. You've already said it's worse than it might even be, so you wanna be careful before you go down that road. 9:52 When you see the triggers that could possibly lead to MIC, go through the steps. 9:57 Collect the additional data, look at the additional triggers, and see if that's really the direction it's going because many times you'll find that it actually isn't. 10:08 This is the part to know because it's the actual test and almost nobody discusses it. TM0212 states that to validate MIC as the cause of internal corrosion, three conditions must be met. 10:22 TM0106 lists the same three for external corrosion. Not two, not a high count plus a hunch. Three. Condition one, elevated organisms relative to somewhere else. 10:39 Absent known or suspected outside contamination, you have to demonstrate increased levels of specific types of viable organisms associated with the corrosion compared against samples taken outside the corroded area. 10:53 A number from the corroded area by itself satisfies nothing. The clause is comparative, so you need samples from outside the corroded area to measure against. Good practice supplies the rest. 11:06 Same handling, same media vendor and formulation, same incubation. This is probably the most important condition. 11:14 Just sampling right by where you see the corrosion or where you've got fluids or sludge by itself doesn't tell you anything. It can't satisfy this condition because it's a comparative clause. 11:27 So if your trigger says, "If I see four vials change on SRB, then I'm injecting chemicals," you haven't met even the very first condition. 11:36 Wherever we think the problem is, we also need to look at both sides of it, or just outside of it, or somewhere else on the line and show that we're actually elevated where the corrosion is. 11:49 What I've found in my experience many times is that they'll have some internal corrosion, and they'll get a little bit of bacteria there. 11:56 Then you test somewhere else in the system further out, and it's the same level of bacteria. That's a good indication the bacteria is not causing the corrosion. That's something else going on. Condition two, 12:10 chemical indicators that support the biology. Chemical indicators in the corroded area have to corroborate the microbiological evidence. 12:20 The standard's examples are elevated sulfide or sulfur in the pit deposits for sulfate reducers and organic acids for acid producers. The chemistry has to agree with what the microbiology says. 12:33 The article has a picture of that. It's an element map of a corrosion deposit under the electron microscope with the sulfur lit up in orange. That's what condition two looks like on paper. 12:46 The way I'd put it is the bacteria don't eat the steel. It's the reaction from the bacteria multiplying in that specific spot. The byproduct of that is what actually makes the corrosive environment. 12:59 So you need something out of the corroded area that shows that byproduct is there. Condition three, biotic factors identified as the primary contributor. This is the one that does the work. 13:13 The objective is to establish that biotic conditions, living organisms, were the predominant contributor to the corrosion in front of you. 13:21 Abiotic factors must be considered in every case, and the nature of the damage should be consistent with the organisms found, with their byproducts, or with their physical influence on the formation of corrosion cells. 13:34 The standard is candid about why that step is hard. It is often difficult to tell the biotic and abiotic contributions apart in localized corrosion. 13:44 Under deposit corrosion, a concentration cell under those same solids, low pH from dissolved carbon dioxide, any of these produces pitting in the same place bacteria are living. 13:56 A line can have more than one mechanism running at once, and where that happens, the standard asks you to establish the relative contribution of each so the mitigation matches the problem. 14:07 Deciding which one predominates is a judgment built on integrated data. It is not a vial count. So the damage has to be consistent with the organisms and their byproducts. It should look like what MIC looks like. 14:21 There are good pictures of that in the standards and plenty online. 14:25 I don't think we got a great one in the article, and that kinda disappoints me because we've got lots of them, but I can't always use other clients' information in the newsletter. 14:35 I can't be airing everybody's dirty laundry. [laughs] Now, something about the vials themselves. Here's the reality of how this step works. 14:46 You'll have a corrosion technician go out in the field, do the sampling, inject the vials, put them back in the box, and nobody opens the box for twenty-eight days. 14:57 If that box is coming to our lab, one of the first things our lab technicians do is open it and look. 15:04 If some of the vials have already started turning right away, especially on the same day they were sampled, that's not necessarily a positive vial. The standard says the same thing. 15:15 A vial that blackens in the first two hours is not a positive. Those are not counted because the blackening comes from sulfide already in the water, not from anything growing. 15:26 What you're basically doing with those vials is injecting colonies of bacteria through a serial dilution and trying to get an estimate of how many colonies are there. The red ones are the APB vials. 15:38 The clear ones that turn black are the SRB vials. It's not a perfect science. There's some subjectivity in reading them, and it's more of a screening tool to see what's out there. 15:50 And on the SRB vials, you wait till the twenty-eighth day to see which vials have turned. That one's not a preference. 15:58 SRB vials shall not be scored as negative until twenty-eight days, and shall is mandatory language in a NACE standard. 16:07 The phenol red vials run on a different clock, day one to day fourteen, and they can be discarded after that. Two windows, one kit. 16:16 And the count you write on the form is an order of magnitude estimate from a method that reads low in bands the standard itself calls too tight. Useful, not precise. Never meant to carry a diagnosis alone. 16:31 This next part is a really important part of the article, and it has to do with where you sample. The bacteria that are a problem, if you truly have MIC, are generally attached to the wall where the steel is. 16:45 They're not necessarily just floating in the fluids and the sludge you get out of the pipeline. So where you sample is very important. 16:55 Anytime we have the opportunity to swab the internal surface of the pipe or get something up against the pipe or swab the surface of an internal corrosion coupon, that's always considered better than just getting the fluids out of the pipe and sampling those. 17:10 We're not saying sampling the fluids is wrong by any means. It's always useful data, and I'd definitely do that in lieu of not being able to do anything. 17:20 But if you have the opportunity to do either one, I'd take a swab off the inside of the pipe. An internal corrosion coupon is a great example. 17:30 If you can get a coupon down in that same environment, preferably in the lower half of the pipe, it's in the same situation the bottom of the steel is in, and those bacteria will attach and grow on the coupon. 17:43 Swabbing the coupon is always better than getting fluids out. I always tell the guys, "If you're going to inoculate a set of bacteria vials, I'd rather you swab the coupon and inoculate from that." 17:55 There's a procedure for it, and it goes a little deeper than this article does. But the free-floating bacteria aren't nearly as much of a concern as the ones attached to the wall. 18:05 Maybe none of them are a concern, but the ones attached to the wall are the ones that could be leading toward MIC. That's the third MIC rule in the field guide. 18:15 Surface samples are far more meaningful than bulk liquid samples. The reasoning is straightforward. 18:22 Free-floating organisms in the bulk fluid have little effect on the corrosion of a surface, and the numbers and types in the liquid are seldom representative of what's living in the biofilm on the wall. 18:33 Corrosion happens on surfaces. Biofilms form on surfaces. 18:39 The organisms that matter are the attached ones, sitting under deposits where they can occlude the surface, fix anodic sites, concentrate acidic species, and shift the local chemistry. 18:50 Pigging returns, coupons, and removable components exposed to the stream are the practical routes to a surface sample, and TM0194 is firm on the handling. 19:01 Testing on attached samples must be performed immediately upon removal from the system. There's one more reason a bulk reading can mislead. Organisms flourish in micro-niches. 19:14 A line can run clean across the great majority of its length and still be under attack in one short section because the environment that supports the attack exists only there. 19:24 A bulk liquid sample answers a question about the fluid. The corrosion is on the wall. 19:31 Another distinction that comes up in the article is that there is no threshold number, and that's exactly why the comparative sampling matters. 19:40 You'll see a lot of pipeline operators, even in their internal corrosion manual, with a threshold number. They'll say, "If it turns more than three vials, we inject chemicals." 19:51 That's just not the best way to go about it because sometimes that level was always going to be there, and it was never going to cause internal corrosion. Maybe you're just spending money on chemicals you don't need. 20:03 It's worth looking into, and sometimes that calls for an actual internal corrosion study. The NACE documents we lean on, TM0194 and TM0212, don't give a universal number. 20:18 They don't say more than this is bad and less than this is good. They talk about the conditions. The counts are for trending. 20:28 They tell you where to look, and they let you compare one spot against another and one date against another. They don't answer the question by themselves. The standard puts it this way: 20:40 Key performance indicators are usually system-specific, and trending data over time, alongside documented operational changes, is usually a more dependable basis for monitoring than absolute values. 20:53 A threshold also depends on the technique that produced it. Values aren't interchangeable between methods, so a figure built on serial dilution SRB counts is likely different from one built on qPCR. 21:07 Counts and trends tell you where to look and whether mitigation is moving the needle. They don't close the question. That's why the three conditions exist. And TM0212 closes the loop at the other end. 21:22 Simply reducing the number of viable microorganisms in a system, with a biocide for instance, should not be equated with controlling internal corrosion in that system. That flip side is true too. 21:34 The biocide might be killing a bacteria, but that doesn't mean you're mitigating internal corrosion because the bacteria might not have been the problem in the first place. 21:44 That's the basis of what I keep repeating here, and it's really what the whole article comes down to. A short illustration with realistic numbers. An ILI call brings you to a dig. 21:57 The cutout shows pitting under a band of black solids along the bottom of the pipe. You collect from the corroded area, solids from inside the pit deposit, a scrape of the film, and fluid. 22:09 Then you move along the same joint to clean wall with no corrosion, and you collect the same three sample types the same way into vials from the same lot. Here's what comes back. 22:21 SRB at day 28, four vials turned in the corroded area, which the table calls 10 to the fourth per milliliter, and four vials turned in the reference area. 22:32 APB at day 14, three vials in the corroded area and three vials in the reference. Identical. Condition one is not met, and the MIC diagnosis stops there, no matter how healthy those counts look in isolation. 22:49 What you have is a system with bacteria in it and localized corrosion that needs a different explanation. 22:55 The solids band and the pit location under it point toward deposits, and the next questions are about water accumulation, flow, and cleaning rather than about biocide. Now change one number. 23:08 The corroded area comes back with six vials turned against three in the reference. Three more vials is three more orders of magnitude. Condition one is met. 23:20 Now you go to the deposit chemistry, looking for sulfide or sulfur in the pit material, and to the pit morphology for damage consistent with what sulfate reducers do. 23:30 If the sulfide is there and the morphology fits, you've got conditions two and three in hand and a call you can defend. Same fieldwork either way. The reference sample is what turns it into evidence. 23:43 That's the correct way to do it. A corroded area and a reference area, a comparative measurement. And when the same number of vials turn in both, the corroded area might not be the bacteria. 23:55 There are a lot of other reasons for internal corrosion. There could be liquid water just sitting there, adding an electrolyte to the inside of the pipeline. That doesn't have anything to do with bacteria. 24:07 It has to do with the operation of the pipeline and whether they need to dry it out or clean it out. The article ends with that one-page field reference, and I think it's excellent. 24:18 It's the three conditions, where they come from, what evidence carries weight, and the common traps on one page. 24:26 If you go to the article on the newsletter site and scroll all the way to the bottom, there's a link to download it. It's a one-page PDF, and as far as I know, it stays there for good. 24:37 The full write-up with the standards behind it is on the newsletter site. Field Notes from RCS, Article 75, MIC: A Positive Vial is Not a Diagnosis. 24:48 And if you're a subscriber and you're logged in, you can comment directly on the article. We see every one of those comments. A question, something to add, something we got wrong, folks are more than welcome. 25:02 Until next time, this is Mike Roberts with Roberts Corrosion Services, and we'll see you on the next one. [outro music]